Beckhoff motor controllers are the most complex in use at ISIS and will be the standard going forward. A Beckhoff controller is basically a generic PLC that includes a number of useful functions out of the box for running motors. The generality of a beckhoff means that it will most likely be used in the future for measuring and controlling other hardware outside of motion. A more detailed presentation has been given about Beckhoffs in a Code Chat entitled Layers, Onions and Ogres.

Documentation

Code on the controller

Unlike most other devices (except the Galil) the computing group has some oversight over the PLC code written on the controller. It has been agreed that this code will mostly be written by IDD, with oversight from computing to guide good programming practices, assist in debugging etc. The ISIS first version of this code is stored at https://github.com/ISISComputingGroup/BeckhoffPLCCode/, which has an accompanying wiki to discuss specifics of the codebase. However, going forward the code will be written in collaboration with the ESS and stored here.

Building and simulating the code

Beckhoff code can be run as a simulated system on a developer machine by doing the following:

  1. Download and install TwinCAT 3 XAE more information can be found about this here (click TwinCAT 3 on the left). If you do not have permission ask IDD. The XAE is really just a Visual Studio plugin.
  2. Start the Twincat XAE. This can be done by clicking on the TwinCat icon in the system tray.
  3. Open the Twincat project that you are interested in. For example the PLC_solution here
  4. Ensure that you have the following toolbars enabled in the XAE (Tools > Customize...):
    • TwinCAT PLC
    • TwinCAT XAE Base
    • (optionally) TwinCAT XAE Remote Manager
  5. Click the Activate Configuration button Activate - Note you may need to do this if it moans about ticks. You may also need to disable Hyper-V and disable Intel Virtualisation from within BIOS on your machine if this error persists.
    To revert this run: Enable-WindowsOptionalFeature -Online -FeatureName Microsoft-Hyper-V -All in an elevated Powershell window. You may also need to execute win8settick.bat in C:\TwinCAT\3.1\System as administrator and reboot.
  6. TwinCAT will ask you to enter a code to get a trial license. You will need to do this once a week.
  7. If prompted if you wish to start the system in Run Mode click Ok. Otherwise start run mode using the button next to Activate Configuration Run
  8. You now have a simulated beckhoff PLC running on your PC. This behaves the same as real hardware and so all development can be done against it. You could now also run an IOC up talking to this local PLC.
  9. To see what is happening inside this PLC in more detail, and to change values, you can use the login button Login

Continuous Integration

Beckhoff PLC code is being developed by people who do not have CI expertise and have their own repository structures yet we want integration into some form of CI to be as easy as possible. This lent itself to the following structure:

  • A BeckhoffTestRunner repository that is owned by us and contains the jenkinsfile and other utilities required for CI
  • Every branch on this repository (apart from master) then pulls a different PLC project down (note each project could be from a different repository or from separate branches on the same repository)
  • The jenkinsfile can then do the one or both of the following:
    • Build the project (currently assumed to be called solution.sln at the top of pulled PLC project)
    • Run any IOCTestFramework tests (currently assumed to be in a tests folder at the top of the pulled PLC project) - these will likely be written by us

This means that the workflow for adding new PLC projects into CI is:

  1. A PLC developer writes their code (making sure the solution is called solution.sln)
  2. They give us a link to the repo and branch that contains the code
  3. We create a new branch on BeckhoffTestRunner and modify it to point at their repo
  4. At this point they have CI for building their code
  5. We make a decision about whether the code requires any system tests and if so add some into their repository

To actually run tests we use the Beckhoff automation interface which can do any of the things you can do in the Twincat XAE automatically through DCOM. AC# (Beckhoff do not fully support a Python interface 😢) program (twinCATAutomationTools) has been written to leverage this interface in the following way to write integration tests for the Beckhoff:

Overview

  1. Jenkins will pull a branch of BeckhoffTestRunner.
  2. build.bat is run to do the following:
    1. Build the TwincatAutomationTools solution, twinCATAutomationTools
    2. Use the twinCATAutomationTools to import the test_config into the generic Twincat Solution and build the PLC code using the automation interface. This build will also create a *.tpy file, which outlines how to connect to the PLC and can be used to configure the IOC itself.
  3. The IOC test framework is started. This will use the TwinCATAutomationTools program to run a local simulated PLC. Then startup and test the Beckhoff twincat in the usual way.

This is currently being run on the ndw1926 node on Jenkins. A quirk of using this DCOM interface is that the Jenkins slave must be run as an interactive user and thus not as a service. To do this there is a bat file that should run on startup inside C:\Users\ibexbuilder\AppData\Roaming\Microsoft\Windows\Start Menu\Programs\Startup.

To run a PLC locally you need a license. A trial license can be activated on a developer's machine by manually running through the building and running steps above until you are prompted to supply a captcha phrase to generate a license.

Testing

Firstly in BeckhoffTestRunner run: git submodule update --init --recursive --remote

To run tests locally you must build the twinCATAutomationTools tools then use them to set up a working simulated PLC. This can be done by running build.bat (best done not in an EPICS terminal).

Once this is done, create an epics terminal, and then run the following command in your BeckhoffTestRunner directory to begin testing:

python %EPICS_KIT_ROOT%\\support\\IocTestFramework\\master\\run_tests.py -tp ".\\tests"

Note that the IOC tests do not stop the PLC at the end of the run, however this isn't a problem as the PLC is restarted when the IOC tests start. If this fails to start the PLC it may be because you do not have a trial license. Debug the issue by manually running through the building and running steps above.

Commissioning steps

These steps are for commissioning a Beckhoff on a beamline.

Networking

Beckhoffs are connected to NDX machines via private networks, in much the same way as the Galils. By convention Beckhoffs live in the 192.168.1.22X range, starting at 1 for the first controller (192.168.1.221)

ADS routes

To actually communicate via the ADS transport layer you will need to set up a route on the instrument PC. To do so:

  1. Install the XAR tools if not already installed. A copy of these will be hosted on <public share>\third_party_installers\special_drivers\beckhoff\. All of the defaults are fine so this should be a case of just clicking through the wizard and installing the drivers that show up.
  2. Set up an ADS route on the NDX:
  • Right-click TwinCAT icon in system tray -> Router -> Edit Routes -> Add... with these settings:
    • Advanced settings ticked, click the IP Address radio button, enter the IP address (mentioned above)
    • Static Target routes and remote routes (default)
    • Everything else can be left as defaults
  1. To confirm that this has been set up remote into the controller itself on the aforementioned IP address and check that the route to the NDX has been added automatically. You should not need to manually add a route in the controller.

IOC setup

The IOC should be able to talk via ADS at this point but will need setting up in the respective configs.

  • A .tpy file will be used for tCioc to actually talk to the hardware via ADS - this should be placed in the instrument's twincat config area
  • A MTRCTRL number will need to be given - this is the normal controller number
  • Beckhoff_plc_code should be specified as a macro, this may be removed in future releases, more information on this is available below however it should be set to 1 for instruments running the latest code.

Fields that aren't automatically populated

Although commissioning a Beckhoff is far simpler than a Galil from an IBEX perspective, there are some fields that need to be set manually for each axis. These are:

These can be set via a caput and will be autosaved thereafter.

Axes, motion setpoints

These are loaded in the usual way, you'll need to put your axes.cmd and motionSetpoints.cmd files alongside the tpy file (in the twincat config directory)

If a controller has more than 8 axes

If a controller with more than 8 axes is going to be used, the TWINCAT IOC will alias records to the next controller number so they are shown in the GUI. For this to work you need to make sure that the next available controller number is not (and never will be, so long as the TWINCAT IOC uses it) used.

IOC(s)

There are currently two IOCs that we have to communicate with Beckhoffs.

The current Beckhoff applications that are being run through tcIOC and the CI pipeline discussed above are:

  • dummy_PLC- a PLC that does very little, basically used to test that fundamental tcIOC comms works
  • old_ISIS_code - this is the old ISIS prototype motion code that is currently on the CRISP jaws. Hopefully this code can be removed once the jaws are moved on.
  • ESS_base_code (now linked to by main of the BeckhoffTestRunner repository) - this is the collaboration code that we will be using go forward.

MCAG (defunct)

This IOC was originally written by ESS. It uses an ASCII protocol over TCP/IP to do the communication and is very specifically designed for motion. There is a simulator which can be run using the following steps:

  • cd EPICS\support\MCAG_Base_Project\master\epics\simulator
  • doit.bat
  • Start the IOC (host macros needs to be set to 127.0.0.1:5024)

Currently this is only being run on IMAT. It should soon be replaced by the collaboration code. - It has been replaced by the new code, so is now defunct.

Beckhoff config area

The config area contains a directory used for storing .tpy files for use with tcIoc. On an instrument it should look like this: \instrument\settings\config\<instname>\configurations\twincat\. The TWINCAT IOC will search in this directory using the given TPY_FILE macro. The generated DB file also gets created in this directory by tcIoc.

Updating

Some discussion has been had on how we handle updates to the Beckhoff PLC code and tcIoc etc. this is documented here