Update Rule23-1.md #1434

Open
wants to merge 4 commits into
base: develop
Choose a base branch
from
Open
Changes from all commits
Commits
File filter

Filter by extension

Filter by extension

Conversations
Failed to load comments.
Loading
Jump to
Jump to file
Failed to load files.
Loading
Diff view
Diff view
15 changes: 6 additions & 9 deletions docs/section23/Rule23-1.md
Original file line number Diff line number Diff line change
Expand Up @@ -4,7 +4,7 @@
**Schema Version:** 0.0.34
**Mandatory Rule:** TRUE
**Rule ID:** 23-1
**Rule Description:** System 2 and 4 - Electric air-source heat pumps shall be modeled with electric auxiliary heat and an outdoor air thermostat. The systems shall be controlled to energize auxiliary heat only when the outdoor air temperature is less than 40°F. The air-source heat pump shall be modeled to continue to operate while auxiliary heat is energized.
**Rule Description:** System 2 and 4 - Electric air-source heat pumps shall be modeled with electric auxiliary heat and an outdoor air thermostat. The systems shall be controlled to energize auxiliary heat only when the outdoor air temperature is less than 40°F.
**Rule Assertion:** B-RMR = expected value
**Appendix G Section:** Section 23 Air-side
**90.1 Section Reference:** G3.1.3.1 Heat Pumps (Systems 2 and 4)
Expand Down Expand Up @@ -35,17 +35,14 @@
**Rule Logic:**
- get the hvac system from the hvac_system_id: `hvac_system = get_component_by_id(hvac_system_id)`
- get the heating system: `heating_system = hvac_system.heating_system`
- get the heatpump_low_shutoff_temperature = `heatpump_low_shutoff = heating_system.heatpump_low_shutoff_temperature`
- get the auxiliary heat high temperature shutoff = `aux_heat_high_temp_shutoff = heating_system.heatpump_auxilliary_heat_high_shutoff_temperature`
- get the auxiliary heat energy source: `aux_heat_energy_source = heating_system.heatpump_auxilliary_heat_type`

**Rule Assertion:**
- Case 1: The system type is 2 and the heatpump_low_shutoff is <= 17F, PASS: `if system_type == HVAC_SYS.2: if heatpump_low_shutoff <= 17: PASS`
- Case 2: The system type is 2 and the heatpump_low_shutoff is >25F, FAIL, provide a message: `elif system_type == HVAC_SYS.2:`
- `if heatpump_low_shutoff > 25: FAIL; note = "Fail because low temperature heat pump shutoff is above 25F for system 2. The modeled low temperature heat pump shutoff value is " + heatpump_low_shutoff
+ "."`
- Case 3: the system type is 2 and the heatpump_low_shutoff is between 17F and 25: UNDETERMINED; provide a message: `else: UNDETERMINED; note = "Undetermined because the low temperature shutoff is between 17F and 25F for System Type 2. Check with the rating authority to ensure correct shutoff temperature. Low shutoff temperature is currently modeled at: " heatpump_low_shutoff = "."`
- Case 4: the system type is 4 (we already know it's 4, because we've checked the 3 SYS 2 cases above), and the low shutoff temperature is <=10F: PASS: `if heatpump_low_shutoff <= 10F: PASS`
- Case 5: anything else, FAIL: `ELSE: Fail`
- Case 1: The auxiliary heat high temperature shutoff is greater than 40F, or the auxiliary heat energy source is anything other than electricity - FAIL: `if (aux_heat_high_temp_shutoff > 40) or (aux_heat_energy_source != "ELECTRIC_RESISTANCE"): FAIL`
- Case 2: All other cases: PASS: `else: PASS`

-
**Notes:**

**[Back](../_toc.md)**